Wednesday, May 2, 2012

ANSI/TIA -568-C Wiring Schemes T568A and T568B



ANSI/TIA-568-C does not sanction the use of the USOC scheme. Instead, two wiring schemes are specified, both of which are suitable for either voice or high-speed LAN operation. These are designated as T568A and T568B wiring schemes.
Both T568A and T568B are universal in that all LAN systems and most voice systems can utilize either wiring sequence without system errors. After all, the electrical signal really doesn't care if it is running on pair 2 or pair 3, as long as a wire is connected to the pin it needs to use. The TIA/EIA standard specifies eight-position, eight-contact jacks and plugs and four-pair cables, fully terminated, to facilitate this universality.
The T568B wiring configuration was at one time the most commonly used scheme, especially for commercial installations; it is shown in Figure 1. The TIA/EIA adopted the T568B wiring scheme from the AT&T 258A wiring scheme.

 
Figure 1: The T568B wiring pattern
The T568A scheme (shown in Figure 10.9) is well suited to upgrades and new installations in residences because the wire-termination pattern for pairs 1 and 2 is the same as for USOC. Unless a waiver is granted, the U.S. government requires all government cabling installations to use the T568A wiring pattern. The current recommendation according to the standard is for all new installations to be wired with the T568A scheme.

 
Figure 2: The T568A wiring pattern
The wire colors and the associated pin assignments for the T568B wiring scheme look like this:
Pin
Wire Color
1
White/orange
2
Orange
3
White/green
4
Blue
5
White/blue
6
Green
7
White/brown
8
Brown
The pin assignments for the T568A wiring schemes are identical to the assignments for the T568B pattern except that wire pairs 2 and 3 are reversed. The T568A pattern looks like this:
Pin
Wire Color
1
White/green
2
Green
3
White/orange
4
Blue
5
White/blue
6
Orange
7
White/brown
8
Brown
Note that when you buy eight-position modular jacks, you may need to specify whether you want a T568A or T568B scheme because the jacks often have IDC connections on the back where you punch the pairs down in sequence from 1 to 4. The jacks have an internal PC board that takes care of all the pair splitting and proper alignment of the cable conductors with the pins in the jack. Most manufacturers now provide color-coded panels on the jacks that let you punch down either pinout scheme, eliminating the need for you to specify (and for them to stock) different jacks depending on which pinout you use.
Tip 
Whichever scheme you use, T568A or T568B, you must also use that same scheme for your patch panels and follow it in any cross-connect blocks you install. Consistency is the key to a successful installation.
Be aware that modular jacks pretty much look alike even though their performance may differ dramatically. Be sure you also specify the performance level (e.g., Category 3, Category 5e, Category 6, Category 6A, etc.) when you purchase your jacks.
When working with ScTP wiring, the drain wire makes contact with the cable shield along its entire length; this provides a ground path for EMI energy that is collected by the foil shield. When terminating ScTP, the drain wire within the cable is connected to a metal shield on the jack. This must be done at both ends of the cable. If left floating or if connected only on one end, instead of providing a barrier to EMI the cable shield becomes a very effective antenna for both emitting and receiving stray signals.
In a cable installation that utilizes ScTP, the plugs, patch cords, and patch panels must be shielded as well.

Tuesday, August 23, 2011

TIA/EIA Recommendations for Telecommunications Rooms



The TIA/EIA does not distinguish between the roles of telecommunications rooms for its published standards. The following is a summary of the minimum standards for a telecommunications wiring room per the ANSI/TIA-569-B Commercial Building Telecommunications Pathways and Spaces Standard:
  • The telecommunications room must be dedicated to telecommunications functions.
  • Equipment not related to telecommunications shall not be installed in or enter the telecommunications room.
  • Multiple rooms on the same floor shall be interconnected by a minimum of one 78(3) (3 or 78mm opening) trade-size conduit or equivalent pathway.
  • The telecommunications room must support a minimum floor loading of 2.4 kilopascals (50 lbf/ft2).
The equipment room is used to contain the main distribution frame (the main location for backbone cabling), phone systems, power protection, uninterruptible power supplies, LAN equipment (such as bridges, routers, switches, and hubs), and any file servers and data processing equipment. TIA-569-B recommends a minimum of 0.75 square feet of floor space in the equipment room for every 100 square feet of user workstation area. You can also estimate the requirements for square footage using Table 1, which shows estimated equipment-room square footage based on the number of workstations.
Table 1: Estimated Square Foot Requirements Based on the Number of Workstations 
Number of Workstations
Estimated Equipment Room Floor Space
1 to 100
150 square feet
101 to 400
400 square feet
401 to 800
800 square feet
801 to 1,200
1,200 square feet


Note 
The floor space required in any equipment room will be dictated by the amount of equipment that must be housed there. Use Table 1 for a base calculation, but don't forget to take into account equipment that may be in this room, such as LAN racks, phone switches, and power supplies.
Here are some additional requirements:
  • There shall be a minimum of two dedicated 120V 20A nominal, nonswitched, AC duplex electrical-outlet receptacles, each on separate branch circuits.
  • Additional convenience duplex outlets shall be placed at 1.8 meter (6) intervals around the perimeter, 150mm (6) above the floor.
  • There shall be access to the telecommunications grounding system, as specified by ANSI/TIA-607-B.
  • HVAC requirements to maintain a temperature the same as the adjacent office area shall be met. A positive pressure shall be maintained with a minimum of one air change per hour or per code.
  • There shall be a minimum of one room per floor to house telecommunications equipment/cable terminations and associated cross-connect cable and wire.
  • The telecommunications room shall be located near the center of the area being served.
  • Horizontal pathways shall terminate in the telecommunications room on the same floor as the area served.
  • The telecommunications room shall accommodate seismic requirements.
  • Two walls should have 20mm (¾) A-C plywood 2.44m (8) high.
  • Lighting shall be a minimum of 500 lx (50 footcandles) and mounted 2.6m (8.5) above the floor.
  • False ceilings shall not be provided.
  • There shall be a minimum door size of 910mm (36) wide and 2,000mm (80) high without sill, hinged to open outward or slide side-to-side or be removable, and it shall be fitted with a lock.
Although these items are suggestions, we recommend that you strive to fulfill as many of these requirements as possible. If your budget only allows for a few of these suggestions, grounding, separate power, and the ventilation and cooling requirements should be at the top of your list.

Wednesday, June 8, 2011

Telecommunications Industry Association (TIA) | Standards and Specification Organizations


The Telecommunications Industry Association (TIA) is a trade organization that consists of a membership of over 1,100 telecommunications and electronics companies that provide services, materials, and products throughout the world. The TIA membership manufactures and distributes virtually all the telecommunication products used in the world today. TIA's mission is to represent its membership on issues relating to standards, public policy, and market development. The 1988 merger of the United States Telecommunications Suppliers Association (USTSA) and the EIA's Information and Telecommunications Technologies Group formed the TIA.
The TIA (along with the EIA) was instrumental in the development of the ANSI/TIA/EIA-568 Commercial Building Telecommunications Cabling Standard. TIA can be found on the Web at www.tiaonline.org.